SECTION 04240
AUTOCLAVED AERATED CONCRETE UNITS
Date:
SECTION REQUIRES EDITOR TO MAKE SELECTIONS -
GENERALLY SELECTIONS ARE
PRECEDED BY **. SPEC EDITOR
TO DELETE INAPPROPRIATE INFORMATION.
PART
1 - GENERAL
SELECT APPROPRIATE SECTIONS FOR BELOW; DELETE
OTHERS
1.01 SUMMARY
A. Section includes, but is not limited to:
Fabrication, transportation, and erection of
Autoclaved Aerated Concrete
(AAC) units.
B. Related sections:
1. Section 01630: Product Substitution Procedures.
2. Section 03200: Concrete Reinforcement.
3. Section 03300: Cast-in-Place Concrete.
4. Section 04070: Masonry Grout.
5. Section 04210: Brick.
6. Section 07600: Flashing and Sheet Metal.
7. Section 07650: Flexible Flashing.
8. Section 07840: Firestopping.
9. Section 07920: Joint Sealants.
10. Section 08110: Steel Doors and Frames.
11. Division 9: Finishes
12. Division 15: Mechanical.
13. Division 16: Electrical.
1.02 REFERENCES
A. Standards of the following as referenced:
1. American Concrete Institute (ACI).
2. ASTM.
3. The Masonry Society (TMS).
4. Underwriters Laboratories, Inc. (UL).
1.03 DEFINITIONS
A. Terms:
1. AAC unit: Autoclaved Aerated Concrete Unit.
2. Bed joint: Horizontal mortar joint between
two AAC units.
3. Head joint: Vertical joint between two AAC
units.
4. AAC ValuBlock:
Nominally rectangular face AAC unit, 24" (608mm) by 24" (608mm).
5. AAC block: Nominally rectangular face AAC
unit, 24" (608mm) by 8" (200mm).
6. Strength Class: Classification that defines
the physical properties of the AAC,
designated
as AC2, AC4, or AC6.
1.04 SUBMITTALS
A. Quality control submittals:
1. Certificate from the AAC manufacturer indicating
AAC product is manufactured in
accordance
with ASTM C 1386.
1.05 QUALITY ASSURANCE
A. Furnish AAC units
from single manufacturer.
B. Mock-ups:
1. Lay 6’-0" long by 4’-0" high sample
wall with AAC units. Orient wall as directed by
Architect.
2. The following items are to be approved:
a. Mortar joints.
b. Control joint complete with joint sealant.
c. Workmanship.
d. Reinforcement, if required.
e. Flashing.
f. Exterior finishes.
g. Interior finishes.
3. Prepare sample wall at least 14 days prior
to beginning AAC unit work. Should wall be
disapproved,
prepare additional walls until approved by Architect.
4. Maintain wall throughout work as standard
of AAC unit work. Do not destroy wall until directed by Architect.
1.06 DELIVERY, STORAGE, AND HANDLING
A. Storage and protection:
1. Offload AAC units and store using pallets
resting on ground. Placing AAC units in
direct
contact with earth is prohibited.
2. Protect AAC units from oil and chemical staining.
1.07 PROJECT CONDITIONS
A. Cold and hot weather installation practices:
1. Cold weather precautions for AAC masonry
work:
a. When temperature of AAC units is below 20°F,
do not install.
b. Remove visible ice on AAC units prior to
installation.
c. Heat mortar sand or mixing water to produce
mortar temperatures between 40°F and
120°F at time of mixing. Maintain mortar temperature above freezing
until placed.
d. Ambient temperature requirements:
1) Between 25°F and 20°F: Use heat sources on
both sides of AAC walls under
construction.
Install wind breaks when wind velocity is in excess of 15 mph.
2) Below 20°F: Provide enclosure for AAC walls
under construction. Use heat
sources
to maintain temperatures above 32°F within enclosures.
e. Daily mean temperature requirements:
1) Between 40°F and 32°F: Protect completed
AAC walls from rain or snow by
covering
with weather resistive membrane for a minimum of 24 hours after
construction.
2) Between 32°F and 25°F: Completely cover completed
AAC walls with weather
resistive
membrane for a minimum of 24 hours after construction.
3) Between 25°F and 20°F: Completely cover completed
AAC walls with
insulating
blankets or equal protection for a minimum of 24 hours after
construction.
4) Below 20°F: Maintain AAC wall construction
above 32°F for 24 hours after completion by enclosure with supplementary heat,
electric heating blankets, infrared heat lamps, or other acceptable methods
outlined to Architect.
2. Hot weather precautions for AAC masonry work:
a. When erected in ambient air temperature of
100°F or ambient air temperature of 90°F with wind velocity in excess of 8
mph, implement the following:
1) Protect AAC wall construction from direct
exposure to wind and sun.
2) Spreading mortar beds more than 4’-0"
ahead of AAC units is prohibited.
3) Setting AAC unit more than one minute after
spreading mortar is prohibited.
1.08 SEQUENCING AND SCHEDULING
A. Loading AAC unit walls or columns is prohibited
prior to the following:
1. Uniform floor or roof loads: 12 hours, minimum.
2. Concentrated loads: Three days, minimum.
B. Construction activities coordination specified
in other Sections for work built into walls:
1. Work required under this Section includes
chase and routing coordination with
construction
activities specified in other Sections.
2. As walls are completed, coordinate with work
required in other Sections for chases or
routing
areas required in AAC walls for electrical, plumbing, and other items.
3. Request relevant construction activities
to mark actual routing or chase locations;
include
required depth.
4. Filling in chases and routed areas specified
in other Sections.
PART
2 – PRODUCTS
2.01 MANUFACTURERS
A. Manufacturers:
1. Acceptable manufacturer: AERCON Florida LLC.;
3701 C.R. 544,
33844; Telephone: (863) 422-6360; Fax (863)
422-6361.
TYPICALLY, USE BELOW IF CLOSED SPEC
2. Substitutions for products listed are prohibited.
USE THIS SUBPARAGRAPH FOR ALLOWING SUBSTITUTIONS
WITHOUT NAMING OTHER
MFRS.
3. Products of other manufacturers similar in
type, quality, and performance are acceptable,
subject
to compliance with specified **
** requirements.
** requirements and
submission of required data indicated in Product Substitution
Procedures section.
2.02 MANUFACTURED UNITS
A. AAC units:
1. Composition: Autoclaved aerated concrete
mixture consisting of quartz sand, lime,
cement,
proprietary additives, and water.
SELECT APPROPRIATE THICKNESS (ES) AND USE; DELETE
OTHERS; SEVERAL DIFFERENT
WALL THICKNESSES REQUIRE MULTIPLE SELECTION. SELECT STRENGTH CLASS (ES)
REQUIRED.
2. Nominal dimensions: **
a. AAC
Block; Tongue and Groove: **4" (100mm) ** 6" (150mm) ** 8"
(200mm) ** 10" (240mm) ** 12" (300mm) ** nominal widths by 8"
(200mm) nominal height by 24" (610mm) nominal length; Strength Class
** AC2. ** AC4. ** AC6. **
b. AAC
Block; Flat face head joints: **4" (100mm) ** 6” (150mm) ** 8"(200mm)
** 10" (240mm) ** 12” (300mm) ** nominal widths by 8” (200mm) nominal
height by 24" (608mm) nominal length; Strength Class ** AC2. ** AC4.
** AC6. **
c. AAC ValuBlock:
**4" (100mm) ** 6" (150mm) ** 8" (200mm) ** 10" (240mm)
** 12" (300mm) ** nominal widths by 24" (608mm) nominal height by
24" (608mm) nominal length; Strength Class ** AC2. ** AC4. ** AC6. **
SELECT APPROPRIATE LINTEL TYPE - SOLID REINFORCED
TYPE OF"U" TYPE
d. Solid lintel units; reinforced: Same width
as walls by ** 8" (200mm) ** 12"
(300mm) ** 16"
(403mm) ** 24" (608mm) ** nominal height; Strength Class AC4.
e. Lintel "U-Block" units: Same width
as walls by ** 8" (200mm) ** 10" (240mm) ** nominal height by 24"
(608mm) nominal length; Strength Class AC4.
B. Fire ratings: In accordance with UL 263,
UL 1479 and UL 2079.
2.03 ACCESSORIES
A. Mortar materials:
1. AAC unit head joint and bed joint mortar;
acceptable product: AERCON Thin Bed
Mortar.
2. Leveling bed mortar: ASTM C 270, Type "M".
3. Aggregate:
a. Leveling bed mortar: Clean, hard, natural,
washed sand in accordance with ASTMC 144.
DELETE SUBPARAGRAPH BELOW IF NO CEMENT GROUT
IS REQUIRED.
a. Masonry grout:
Fine aggregate: ASTM C 404, Size No. 1
Coarse aggregate: ASTM C 404, Size No. 89.
4. Water: Clean, potable, free from deleterious
amounts of alkalies, acids, and organic
materials.
B. Reinforcement: ASTM A 615, Grade 60, deformed
type for #3 and larger bars; actual sizes
indicated
on Contract Drawings.
C. Backer rods and sealants: Specified in Joint
Sealants Section.
D. Flexible flashing: Specified in Flexible
Flashing Section.
E. Fire-rated insulation for penetrations of
rates walls: Specified in Firestopping Section.
F. Tension tie-downs; acceptable manufacturer:
Go-Bolt, Inc.;
G. Fasteners and Anchors: Compatible with AAC
materials.
2.04 MIXES
A. Mortar proportions:
1. ACC unit head joint and bed joint mortar:
Mix in accordance with manufacturer’s
mixing
instructions.
2. Proportion materials by volume in accordance
with ASTM C 270 for leveling course
only.
Use AAC thin bed mortar for head and bed joints and other joints in AAC work.
DELETE GROUT PROPORTIONS PARAGRAPH IF DELETED
ABOVE.
B. Grout proportions:
1. Fine and Coarse Grout: Proportion materials
by volume in accordance with ASTM C
476.
2. Slump: 8" to 11" measured in accordance
with ASTM C 143.
PART
3 - EXECUTION
3.01 PREPARATION
A. Protection:
1. Keep walls dry during erection by covering
at end of each work period with non-staining
waterproof
membrane covering.
2. Protect partially completed walls not being
worked on with non-staining waterproof
membrane
until construction activities specified in other sections completes protection
of
walls.
3. Covering: Overhang at least 2’-0" on
each side of wall; anchor on each side of wall.
4. Protect finished exposed work from stains.
5. Take particular care to keep AAC units clean.
6. Brace walls during construction to protect
from wind damage.
3.02 INSTALLATION
A. Workmanship:
1. Lay AAC units plumb, level, and true to line
for range.
2. Lay units in running bond with 6" minimum
head joints lap in alternate courses.
3. Cut AAC units with unit manufacturer recommended
hand type saw or electric bandsaw
specially
designed for cutting AAC units. Lay out units to minimize
cutting.
B. Building in other work:
1. Install work of other sections required to
be incorporated with AAC units as work
progresses;
include anchors, and accessories. Space and align built-in parts; exercise
care
not to disturb other materials from position.
2. Coordinate with SEQUENCING AND SCHEDULING
Article for required routing and
chases.
3. Fill in interior spaces around built-in items
with fine grout or interior plaster.
4. Fill in exterior spaces around built-in items
with fine grout or stucco.
5. Fill hollow metal frames in AAC unit walls
with fine grout as wall is laid. Rake back
_" joint between hollow metal frame and
adjacent AAC unit to receive sealant at butt
type
frames.
C. Mortar joints:
1. Head and bed joints:
a. Lay first course in full bed of leveling
bed mortar in thickness necessary to level AAC unit top; not less than 3/8
inch.
b. Apply AAC unit head joint and bed joint mortar
on full face of AAC unit already laid.
2. Make adjustment while mortar is still soft
and plastic by tapping to plumb and bringing
to
alignment.
3. Check each AAC unit as laid with mason’s
level for level and plumb with wall below.
4. Remove and replace mortar with fresh mortar,
where adjustment must be made after
mortar
has started to set.
5. Keep bed and head joints uniform in width.
6. Standard thickness for both horizontal and
vertical mortar joints:
a. Base course bed joint: _", nominal,
+/- _".
b. Other vertical coursing and head joints:
1/16", nominal.
7. Take particular care to avoid spreading mortar
on exposed face of AAC unit. Only
normal
mortar droppings will be accepted on face of AAC unit; remove only after mortar
has
dried enough not to smear.
D. Flexible flashing:
1. Clean AAC unit surfaces smooth; maintain
free from projections capable of puncturing
flashing
material.
2. Follow requirements indicated in Flexible
Flashing Section.
E. Joint treatment: Remove excess extruded mortar
immediately after laying AAC unit; tooling
joints
is not required.
F. Control joints:
1. Make joint " wide, unless indicated
otherwise, rake out control joints to depth of 3/4"
while
mortar is still plastic.
2. Provide joints at 24’-0" O.C. unless
otherwise indicated.
3. Leave joint open and clean for caulking in
accord with Joint Sealants Section.
G. Tolerances:
1. Maximum variation from plumb: _" in
10’-0"; not exceeding 3/8" in 20’-0".
2. Maximum variation
from level: _" in 20’-0", not exceeding _" in 49’-0" or
more.
3. Maximum variation in linear building line
from location indicated: _" in 20’-0".
3.03
CLEANING AND PATCHING
A. Keep AAC unit work free of mortar droppings
as work progresses and, at completion of
work,
rub AAC unit to remove excess mortar
B. Patch AAC units with
excessive spalls or chips.
END OF SECTION 04240